Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM04214
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2008 | DAVE MANN | FIRE | REVIEW | Denied | Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. Also, be advised that all E occupancies with an occupant load greater than 50 will require a fire alarm system (separate submittal to fire department) |
| 02/14/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the locations for the water meter and the backflow assembly. |
| 02/19/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Denied | OVER THE COUNTER REVIEW. MARK HAS PLANS AND IS WALKING THROUGH. TO ADDRESS ENGINEERING CONCERNS. |
| 02/19/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 02/20/2008 | GERRY KOZIOL | WWM | REVIEW | Needs Review | |
| 02/20/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/20/2008 | SUE REEVES | OUT TO CUSTOMER | Completed |