Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04214
Parcel: 11508007B

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM04214
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2008 DAVE MANN FIRE REVIEW Denied Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
Also, be advised that all E occupancies with an occupant load greater than 50 will require a fire alarm system (separate submittal to fire department)
02/14/2008 ROBERT SHERRY WATER REVIEW Denied Show the locations for the water meter and the backflow assembly.
02/19/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied OVER THE COUNTER REVIEW. MARK HAS PLANS AND IS WALKING THROUGH. TO ADDRESS ENGINEERING CONCERNS.
02/19/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/20/2008 GERRY KOZIOL WWM REVIEW Needs Review
02/20/2008 CPIERCE1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/20/2008 SUE REEVES OUT TO CUSTOMER Completed