Permit Number: T07CM04213
Parcel: 107083180

Address:
770 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM04213
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Desert Dog Automotive - Building Addition
T07CM04213
Building Plan (3rd Review)

TRANSMITTAL DATE: June 12, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t07cm04213.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
06/12/2008 MARTIN BROWN FIRE REVIEW Approved
06/12/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/24/2008 ROBERT SHERRY WATER REVIEW Approved
06/30/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: July 1, 2008
SUBJECT: Garage Addition - Full Compliance
TO: Antonio Romano
LOCATION: 770 W Grant Road, T14S, R14E, Section 18, Ward 5
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07CM04213 (Third Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP. Be sure to include response letter with next submittal.
2. The most recent aerial photo of the building does not match what is depicted on the site plan. Please modify site plan to represent actual footprint of building and/or clarify. Explain what is going to be done with the storage structures that are on site.
3. Complied
4. Complied
5. Per D.S. 2-02.2.1.4: Location map should provide the following information:
a. Complied
b. Complied
c. Section, township, range
6. Provide lot bearings per D.S. 2-02.2.1.5
7. Complied
8. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. Verify that sight visibility triangles have been accurately depicted on site plan.
9. Add dimensions for parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
10. Provide Traffic engineering signature on site plan - unable to locate signature.
11. Complied
12. Provide Traffic engineering signature on site plan - unable to locate signature..
13. Complied
14. Complied
15. Complied
16. Complied
17. Complied
18. Provide drainage patterns for southern portion of parcel in addition to the drainage arrows already provided in the northern portion of parcel per D.S. 2-02.2.1.16.
19. Complied
20. Complied
21. Complied
22. Complied
23. Complied
24. DS Sec.2-02.2.1.A.19: Label the 9-foot future sidewalk and curb area on the site plan to verify that all improvements are located outside of the future ROW. Clarify bold dashed line on site plan.
25. Complied
26. Complied
27. Complied.
28. Complied
29. Complied
30. Complied
31. Complied
32. Complied
33. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
34. Complied
35. Complied
36. Provide phone number for owner.
37. Complied
38. Complied
39. Complied
40. Complied
41. Provide a dimension for the PAAL that is between the sidewalk, located on the south side of the building and the south property line. It does not appear that the PAAL meets the minimum 24' foot width for a two way PAAL.
42. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
07/03/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Either specify that all conduit be run overhead, or specify the wiring method per NEC 511.4.
2. Either specify that all conduit be run overhead, or specify the required seals per NEC 511.9 and 501.15.
3. Please specify that the receptacles be GFCI protected. Reference NEC 511.12.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/11/2008 GERARDO BONILLA OUT TO CUSTOMER Completed