Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM04213
Parcel: 107083180

Address:
770 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T07CM04213
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Desert Dog Automotive - Building Addition
T07CM04213
Site Plan (2nd Review)

TRANSMITTAL DATE: March 4, 2008

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the entire site due to an expansion greater than twenty-five (25) percent. This plan has been reviewed as a COMMERCIAL SERVICES USE GROUP, Automotive - Service and Repair, Major.

2. This comment has not been addressed. D.S. 2-02.2.1.A.5 Provide lot line bearings on the plan.

3. D.S. 2-02.2.1.A.8 The location of the proposed handicapped sign encroaches into the 2'-6" vehicle overhang, relocate the sign.

4. D.S. 2-02.2.1.A.12 Per D.S. 3-05.2.2.D provide a backup spur at the west end of the northern PAAL and for the PAAL the accesses the parking on the southeast side of the proposed rolling gate.

5. D.S. 2-02.2.1.A.12 Provide a dimension for the PAAL that is between the sidewalk, located on the south side of the building and the south property line. It does not appear that the PAAL meets the minimum 24' foot width for a two way PAAL.

6. D.S. 2-02.2.1.A.12 Per D.S. 2-08 a pedestrian circulation/accessible route are required to all buildings on site. The "SHIPPING CONTAINERS" are considered a building for zoning purposes therefore a pedestrian circulation/accessible route must connect the "SHIPPING CONTAINERS" to the existing building.

7. D.S. 2-02.2.1.A.12 Based on the provided photos there appears to be an air conditioner and electrical meter, on the east side of the building that encroach into the 5' pedestrian refuge.

8. D.S. 2-02.2.1.A.12 Clarify what the "PEDESTRIAN BARRIER" is that is called out on the plan.

9. This comment has not been addressed. Provide the required information on the site plan. D.S. 2-02.2.1.A.13 Zoning acknowledges that an "EXISTING SIGN STANDARD" is shown on the plan. Provide the type, size and height of the existing sign.

10. Provide written conformation from solid waste that the curb side pick-up will be allowed. D.S. 2-02.2.1.A.32 Show the location for the refuse container on the plan.

11. Ensure that all changes to the site plan are reflected on the landscape plan.

12. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t07cm04213-2nd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
03/04/2008 STEVE SHIELDS ZONING HC SITE REVIEW Denied See Zoning Comments
03/18/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. The proposed site improvements, including the paving/striping of the parking area and the addition of the new building area are required to be brought up to current code. A separate landscape plan will be required per DS 2-07.0. to verify that minimum requirements are met for the building expansion and new parking area.

2. Landscape plan shall include irrigation specification design and layout per DS 2-06.5.4.A & DS 2-06.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation.

3. The proposed new parking spaces near the east property line must be screened from Grant Road (MS&R) with a 10-foot wide landscape border and a 30-inch high screen. In addition the proposed parking spaces and relocated shipping containers must be screened from the O-3 zoned property to the north with a 5-foot high wall per screening requirements in LUC Table 3.7.2-I.

4. Canopy trees must be evenly distributed throughout the vehicular use area. Every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk). Indicate parking lot canopy trees on the landscape plan as required. LUC 3.7.2.3.A

5. Both the common and proper/ latin names of all plants proposed must be stated in the plant legend. DS 2-07.2.2.A.1.d

6. Show on site plan the existing and future sight visibility triangles per DS 3-01.5.
DS 2-02.2.2.1.A.10
04/10/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: April 10, 2008
SUBJECT: Garage Addition - Full Compliance
TO: Antonio Romano
LOCATION: 770 W Grant Road, T14S, R14E, Section 18, Ward 5
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07CM04213 (Second Review)


RESUBMITTAL REQUIRED: Site Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP. Be sure to include response letter with next submittal.
2. The most recent aerial photo of the building does not match what is depicted on the site plan. Please modify site plan to represent actual footprint of building and/or clarify. Explain what is going to be done with the storage structures that are on site.
3. Complied
4. Complied
5. Per D.S. 2-02.2.1.4: Location map should cover approximately one (1) square mile, be drawn at a minimum scale of 3" =1 mile, and provide the following information
a. Complied
b. Compllied
c. Section, township, range; section corners; north arrow and scale labeled.
6. Provide lot bearings per D.S. 2-02.2.1.5
7. Complied
8. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
9. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
10. DS Sec.2-02.2.1.A.11 & DS Sec.3-01.3.2.C: Depict and label 25-feet radii concrete curbs per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213) at the driveway entrance along Fort Lowell Road. The curbs should be constructed at the edge of pavement and entirely on the subject property, which must also be depicted on the site plan. If this is not required - provide documentation.
11. Complied
12. DS Sec.2-02.2.1.A.11: Revise the site plan to show the minimum 20-foot separation that is required between adjacent driveways. Refer to Tucson Code (TC) Chapter 25-39 for curb cut and driveway requirements.
13. Complied
14. Complied
15. Complied
16. Complied
17. If loading space is required fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14.
18. Provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
19. Complied
20. DS Sec.2.02.2.1.A.16: Provide drainage arrows and locations of all concentration points. Specifically show roof down spout locations proposed buildings at pedestrian circulation areas. A detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage at all pedestrian sidewalk is required; refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk.
21. Complied
22. Complied
23. Complied
24. DS Sec.2-02.2.1.A.19: Label the 9-foot future sidewalk and curb area on the site plan to verify that all improvements are located outside of the future ROW.
25. Verify that easement of record have been graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20. If these have been addressed provide explanation on response letter.
26. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
27. Provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23. Provide contour interval on plan.
28. Show all fences, walls, or vegetation for screening and sight visibility by type, material, height, location and spacing per D.S. 2-02.2.1.27.
29. Complied
30. Complied
31. Complied
32. Complied
33. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
34. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
35. Complied
36. List the consulting engineer and the owner/developer on the plans with the pertinent information. Information should include a contact name.
37. Indicate all symbols on plans and reference in legend.
38. DS Sec.2-02.2.1.A.8: Provide typical parking space detail for parking areas. Provide site plan parking dimensions, note and parking details for both standard and handicap parking, together with access thereto. See DS Sec. 3-05.2.0.B.1 for minimum parking standards.
39. Verify that all text is a minimum of twelve point font for microfilming and record keeping.
40. Provide documentation from Environmental Services for approval of refuse container service.
41. Provide a dimension for the PAAL that is between the sidewalk, located on the south side of the building and the south property line. It does not appear that the PAAL meets the minimum 24' foot width for a two way PAAL.
42. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
04/15/2008 SHANAE POWELL REJECT SHELF Completed