Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL NEW
Permit Number - T07CM04135
Review Name: COMMERCIAL NEW
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/23/2007 | MARTIN BROWN | FIRE | REVIEW | Denied | From sheet E1.0, the Emergency Power Off switch appears to be too close to the fuel dispensers. Please refer to the 2006 IFC, Section 2203.2 for placement guidelines. |
| 11/05/2007 | SREEVES1 | WWM | REVIEW | Passed | |
| 11/05/2007 | SREEVES1 | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 11/06/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/16/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Please provide drawings with a font size of 1/8". For areas where this is not practicable, adhere to a minimum standard of 3/32". 2. Provide a minimum foundation depth for Detail 3, Sheet E1.0. 3. Provide disconnecting means for the submersible pumps. 4. Specify the provisions to remove all voltage sources during periods of maintenance and servicing of the dispensing equipment. Include cut sheets, wiring diagrams, and equipment locations as appropriate. Reference NEC NEC 514.13. 5. Provide Mechanical and Plumbing Plans. Sheet E2.1 not reviewed. 6. Provide correct caisson size, reinforcement and calculations for light pole OR get permission for deferred submittal from the building official. 7. Please fill in the fault current in the blacked out column. 8. Please fill in the "X" in Series Rating Key Note 3. 9. Series Rating Keynote 2 does not appear to be used. 10. Please note that Tucson Electric Power Company publishes a value of 55,600A Available Fault Current for a 120/208V 800A 3-phase Pad-mount Transformer service. If your TEP contact has confirmed the figure of 42,000 AIC, disregard. |
| 11/19/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Reduced pressure backflow prevention assemblies (for water service to the building and for irrigation, as shown on sheet C4) shall be installed directly after the water meter, not before the water meter. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf 2. Show how backflow protection is being provided for the air/water machine per Section 603, UPC 2006. |
| 11/19/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/20/2007 | TERRY STEVENS | ZONING | REVIEW | Denied | 11/21/07 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. |
| 12/06/2007 | JASON GREEN | ENGINEERING | REVIEW | Denied | Engineering Review: 06DEC07 T07CM04135- 3301 S 6th Avenue This site plan is associated with S07-155, T07CM01074 and T07BU02153. This site plan can not be approved until all comments associated with the Tentative Plat review (S07-155) and Site Plan review (T07CM01074) have been addressed. Please refer to comments posted under each activity for further clarifications of outstanding items that need to be addressed. For further asistance please contact Jason Green, CFM at 837-4929 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/22/2007 | ANY | REJECT SHELF | RECEIVED |