Permit Number: T07CM04135
Parcel: 11901065B

Address:
3301 S 6TH AV

Review Status: Active

Review Details: COMMERCIAL NEW

Permit Number - T07CM04135
Review Name: COMMERCIAL NEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2007 MARTIN BROWN FIRE REVIEW Denied From sheet E1.0, the Emergency Power Off switch appears to be too close to the fuel dispensers. Please refer to the 2006 IFC, Section 2203.2 for placement guidelines.
11/05/2007 SREEVES1 WWM REVIEW Passed
11/05/2007 SREEVES1 MECHANICAL-COMMERCIAL REVIEW Passed
11/06/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/16/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please provide drawings with a font size of 1/8". For areas where this is not practicable, adhere to a minimum standard of 3/32".
2. Provide a minimum foundation depth for Detail 3, Sheet E1.0.
3. Provide disconnecting means for the submersible pumps.
4. Specify the provisions to remove all voltage sources during periods of maintenance and servicing of the dispensing equipment. Include cut sheets, wiring diagrams, and equipment locations as appropriate. Reference NEC NEC 514.13.
5. Provide Mechanical and Plumbing Plans. Sheet E2.1 not reviewed.
6. Provide correct caisson size, reinforcement and calculations for light pole OR get permission for deferred submittal from the building official.
7. Please fill in the fault current in the blacked out column.
8. Please fill in the "X" in Series Rating Key Note 3.
9. Series Rating Keynote 2 does not appear to be used.
10. Please note that Tucson Electric Power Company publishes a value of 55,600A Available Fault Current for a 120/208V 800A 3-phase Pad-mount Transformer service. If your TEP contact has confirmed the figure of 42,000 AIC, disregard.
11/19/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Reduced pressure backflow prevention assemblies (for water service to the building and for irrigation, as shown on sheet C4) shall be installed directly after the water meter, not before the water meter. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Show how backflow protection is being provided for the air/water machine per Section 603, UPC 2006.
11/19/2007 ROBERT SHERRY WATER REVIEW Approved
11/20/2007 TERRY STEVENS ZONING REVIEW Denied 11/21/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
12/06/2007 JASON GREEN ENGINEERING REVIEW Denied Engineering Review:

06DEC07

T07CM04135- 3301 S 6th Avenue

This site plan is associated with S07-155, T07CM01074 and T07BU02153.

This site plan can not be approved until all comments associated with the Tentative Plat review (S07-155) and Site Plan review (T07CM01074) have been addressed. Please refer to comments posted under each activity for further clarifications of outstanding items that need to be addressed.

For further asistance please contact Jason Green, CFM at 837-4929

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2007 ANY REJECT SHELF RECEIVED