11/28/2007 GERRY KOZIOL WWM REVIEW Approved
11/29/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. 12" CMU CLARIFICATION ACCEPTED FOR 2 HOUR FIRE WALL ON PROPERTY HOWEVER, PARAPET MUST EXTEND NO LESS THAN 30" ABOVE ROOF LINE OR 5' HORIZONTALLY. REFERENCE CODE SECTIONS 704.11.4.3 AND/OR 704.11.1.
2. PREVIOUS COMMENT ABOUT HI/LOW WATER FOUNTAIN DID NOT RECCOMEND A CUP DISPENSER SUBSTITUTION. SUBSTITUTION WITH A BOTTLED WATER SYSTEM WITH A CUP DISPENSER MAY ONLY BE DONE WITH APPROVAL FROM BUILDING OFFICAL.
3. CARPORT WALLS AND STRUCTURE SETBACK FALL WITHIN 2 HOUR RATING REQUIREMENT AS PER TABLE 602. SAME AS WITH COMMENT ONE ABOVE.