Permit Number: T07CM04134
Parcel: 127030910

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04134
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2007 DAVE MANN FIRE REVIEW Approved
10/22/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/05/2007 GERRY KOZIOL WWM REVIEW Denied needs 8th floor credit evaluation
11/07/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL COMMENT:
WHEN A CHANGE OF OCCUPANCY IS INITIATED, ALL BUILDING COMPONANTS MUST BE BROUGHT UP TO CODE COMPLIANCE:
1. TABLE 602 REQUIRES THAT BOTH EAST AND EAST EXTERIOR WALLS MUST HAVE A 2 HOUR FIRE RATING.
2. THE SHED COVERING THE REAR SLAB NEEDS TO BE CLARIFIED ON THESE DOCUMENTS.
3. NEED GRADING PLAN TO SHOW ACCESSIBILITY TO SITE AND TO BUILDING ENTRY
4. NEED HI LOW DRINKING FOUNTAIN AS PER ANSI117.2/602.5
STORAGE ROOM NOS. 107 AND 109 NEED TO BE TWO HOUR RATED, TABLE 508.2
5. SINK IN ROOM 105 MUST BE ACCESSIBILE
11/07/2007 ROBERT SHERRY WATER REVIEW Approved
11/07/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water supply plans and isometrics. Reference Section 103.2.3, UPC 2006.
2. Provide the minimum plumbing facilities (i.e. a service sink) required by Table 2902.1 and Section 2902.2, IBC 2006, for mercantile occupancy.
3. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006. http://www.ci.tucson.az.us/tucsonwater/clearwater?output=allTabular
11/07/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2006.
2. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used.
3. Table 6-2, ASHRAE 62-1-2004 indicates that a Zone Air Distribution Effectiveness (Ez) value of 0.8 is required if the ceiling supply of warm air is 15 degrees Fahrenheit or more higher than the space temperature.
11/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/21/2007 DELMA ROBEY OUT TO CUSTOMER Completed
11/21/2007 DELMA ROBEY REJECT SHELF Completed