Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2008 MARTIN BROWN FIRE REVIEW Passed
06/05/2008 WILDAN 2ND PARTY REVIEW REVIEW Denied SHEET P1.2
1. THE FLOOR DRAINS LOCATED IN THE AIR COMPRESSOR AREA WILL REQUIRE TRAP PRIMERS. PLEASE PORVIDE A DETAIL SHOWING THE LOCATION AND POINT OF CONNECTION OF THE TRAP PRIMERS TO THE POTABLE WATER DISTRIBUTION. REFERENCE SECTION 1007.0 2006 UPC.

2. PLEASE PROVIDE A FIXTURE SCHEDULE SHOWING THE ADDED FLOOR DRAINS. NOTE: IF THESE FLOOR DRAINS ARE FOR EMERGENCY DRAINS ONLY THEN PLEASE ANNOTATE ON THE PLAN A ZERO FIXTURE UNIT LOAD. IF THEY WILL RECEIVE ANY DISCHARGE INTO THEM THEN A 2 F.U. VALUE SHALL BE APPLIED. REFERENCE SECTION 103.2.3 2006 UPC.