Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T07CM04127
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2008 | MARTIN BROWN | FIRE | REVIEW | Passed | |
| 06/05/2008 | WILDAN | 2ND PARTY REVIEW | REVIEW | Denied | SHEET P1.2 1. THE FLOOR DRAINS LOCATED IN THE AIR COMPRESSOR AREA WILL REQUIRE TRAP PRIMERS. PLEASE PORVIDE A DETAIL SHOWING THE LOCATION AND POINT OF CONNECTION OF THE TRAP PRIMERS TO THE POTABLE WATER DISTRIBUTION. REFERENCE SECTION 1007.0 2006 UPC. 2. PLEASE PROVIDE A FIXTURE SCHEDULE SHOWING THE ADDED FLOOR DRAINS. NOTE: IF THESE FLOOR DRAINS ARE FOR EMERGENCY DRAINS ONLY THEN PLEASE ANNOTATE ON THE PLAN A ZERO FIXTURE UNIT LOAD. IF THEY WILL RECEIVE ANY DISCHARGE INTO THEM THEN A 2 F.U. VALUE SHALL BE APPLIED. REFERENCE SECTION 103.2.3 2006 UPC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/22/2008 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 07/22/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |