Permit Number: T07CM04120
Parcel: 13416205D

Address:
1041 S KOLB RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04120
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
10/19/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/19/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/19/2007 ROBERT SHERRY WATER REVIEW Approved
10/19/2007 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures
10/19/2007 JASON GREEN ENGINEERING REVIEW Approved
10/22/2007 DAVE MANN FIRE REVIEW Approved
10/22/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM04120 10/19/07

1. Provide an electrical circuit for the new Control Panel. Indicate panel and circuit on electrical plan.
2. Provide a disconnecting means for the new Car Wash Equipment. Reference NEC 430 Part IX.
3. Distinguish new from existing circuits on the panel schedules. Otherwise, they will be reviewed and permitted as if all were new.
4. Provide TEP available fault current.
5. Provide fault calculations for New Panel C.
10/23/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/23/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed