Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/19/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
10/19/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
10/19/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
10/19/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/19/2007 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures |
10/19/2007 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
10/22/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
10/22/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM04120 10/19/07 1. Provide an electrical circuit for the new Control Panel. Indicate panel and circuit on electrical plan. 2. Provide a disconnecting means for the new Car Wash Equipment. Reference NEC 430 Part IX. 3. Distinguish new from existing circuits on the panel schedules. Otherwise, they will be reviewed and permitted as if all were new. 4. Provide TEP available fault current. 5. Provide fault calculations for New Panel C. |
10/23/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/23/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |