Permit Number: T07CM04110
Parcel: 12701003R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM04110
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. APPEAL TO BUILDING OFFICAL TO USED 3/32" LETTING HAS NOT BEEN PRESENTED
2. A SIRTE PLAN MUST BE PRESENTED SHOWING PROPER LOCATION BUILDING, DIMENSIONS, ACCESSIBLE PARKING, ACCESSIBLE ROUTES FROM PUBLIC TRANSPORTATION PLUS ALL GRADES OF ROUTES MEETING IBC 2006 AND ANSI 117.1. NO SITE PLAN NO PERMIT.
3. BUILDING DATA WORK SHEET AS REQUIRED BY DSD STANDRADS AND WEB SITE IS NOT AVAILABLE.
4. ALL RAMP LEVELS AND STAIRS NEED TO BE DETAILED ON DRAWINGS AS MEETING IBC 2006 AND ANSI 117.1
5. NEED STRUCTURAL CALCULATIONS
6. REDO SHEET INDEX TO INCLUDE ALL NEW DRAWINGS ADDED SINCE LAST SUBMITTAL.
7. NEED TO SHOW 20% BEING SPENT 0N ACCESSIBILITY
UP GRADES
01/29/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Any fittings or connections in a drainage system that result in a reduction of the pipe area is prohibited, e.g. the 4" cleanouts between the men's lavatories and the urinals that transition to 3" drains (detail 02/EP-1). Reference Section 316.4.1, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/09/2008 CPIERCE1 OUT TO CUSTOMER Completed
04/09/2008 SHANAE POWELL REJECT SHELF Completed