Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM04110
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/28/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. APPEAL TO BUILDING OFFICAL TO USED 3/32" LETTING HAS NOT BEEN PRESENTED 2. A SIRTE PLAN MUST BE PRESENTED SHOWING PROPER LOCATION BUILDING, DIMENSIONS, ACCESSIBLE PARKING, ACCESSIBLE ROUTES FROM PUBLIC TRANSPORTATION PLUS ALL GRADES OF ROUTES MEETING IBC 2006 AND ANSI 117.1. NO SITE PLAN NO PERMIT. 3. BUILDING DATA WORK SHEET AS REQUIRED BY DSD STANDRADS AND WEB SITE IS NOT AVAILABLE. 4. ALL RAMP LEVELS AND STAIRS NEED TO BE DETAILED ON DRAWINGS AS MEETING IBC 2006 AND ANSI 117.1 5. NEED STRUCTURAL CALCULATIONS 6. REDO SHEET INDEX TO INCLUDE ALL NEW DRAWINGS ADDED SINCE LAST SUBMITTAL. 7. NEED TO SHOW 20% BEING SPENT 0N ACCESSIBILITY UP GRADES |
01/29/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/21/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Any fittings or connections in a drainage system that result in a reduction of the pipe area is prohibited, e.g. the 4" cleanouts between the men's lavatories and the urinals that transition to 3" drains (detail 02/EP-1). Reference Section 316.4.1, UPC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/09/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
04/09/2008 | SHANAE POWELL | REJECT SHELF | Completed |