Permit Number: T07CM04110
Parcel: 12701003R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04110
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2007 DAVE MANN FIRE REVIEW Approved
11/05/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. NEED SITE PLAN SHOWING ACCESSIBILITY PARKING AND ROUTES
2. CODE DATA NEEDS TO BE SHOWN ON SHEET A-001; I.E. BUILDING TYPE, OCCUPANCY, ZONEING, BLDG CLASSIFICATION AND ETC.
3. ARCHITECTURAL FLOOR PLANS NEED TO BE CORRECTED TO SHOW AND REFERENCE MODIFIED TOILET LAYOUT AND DETAILS ON A-601/2.
4. PROBLEMS WITH TOILET PLAN AND LAYOUT; VERTICLE BAR AT TOILET STALLS, ANSI 117.1/604.5.1, URNIAL HEIGHT ANSI 117.1/ 605.2
5. RECONSTRUCTION OF ENTRY LACKS PROPER DETAILING; DETAILED DEMOLITION PLANS AND STRUCTURAL FOUNDATION AND FRAMING PLANS
AND DETAILS
6. CLARIFY AND NOTE REQUIRED SAFETY GLAZING IN NEW FRONT ENTRANCE VESTIBULE
7. DIMENSION ON DETAIL D-2/A-502 IS INCORRECT
8. CONFIRM THAT ALL EXISTING RAMPS COMPLY WITH ANSI 117.1 REQUIREMENTS
9. OCCUPANCY CALCULATIONS INDICATE 320 OCCUPANTS. COPY OF OCCUPANCY SIGN SHOWS 240 OCCUPANTS. IS SAMPLE SIGN INCORRECT?
10. INDICATE NEW MECHANICAL LIFT FOR HANDICAP TO BE INSTALLED ON FLOOR PLAN AND PROVIDE MANUFATURER'S SPECIFICATION AND DETAILS
11. VERIFY THAT ALL STEPS MEETS CODE REQUIREMENTS AS FOR RISER AND TREAD SIZES AND DIMENSIONS.
11/06/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied ELECTRICAL COMMENTS: ELECTRICAL PLANS DENIED FOR FOLLOWING REASONS,
1.SHEET A-201 AND 202, NOTE N16----NEW QUARTZ FLOOD LIGHTS,PROVIDE CIRCUIT DESTINATION,ALSO CANNOT LOCATE ON FIXTURE SCHEDULE.
2. SHEET E 101, PROVIDE PANEL LOCATIONS,PANEL DIRECTORIES, PANEL LOAD CALCULATIONS REGARDING CIRCUITS TO BE USED.
3. SHEET E 101 SHOW LOCATION OF DIMMER SWITCH AND CORRESPONDING CIRCUITS.
4. SHEET E P-1 LIGHT FIXTURES SHOWN AS C-2 AND C-3 NOT ON FIXTURE SCHEDULE.

RAY MAJUTA ELECT PL EX
DSD,520-837-4988
11/13/2007 ROBERT SHERRY WATER REVIEW Approved
11/13/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The plumbing fixture schedules (sheets A-602 and EP-1) indicate a proposed hand sink for the kitchen but no hand sinks are shown on the plans. Are hand sinks part of this project? Reference Section 103.2.3, UPC 2006.
2. Provide specifications for all the proposed floor drains. Reference Section 401.1, UPC 2006.
3. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. flush valves). Reference Section 609.10, UPC 2006.
4. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving urinals require cleanouts regardless of length). Reference Section 707.4, UPC 2006.
5. Provide a vent for each fixture trap (e.g. floor drains). Reference Sections 901.0 and 910.1, UPC 2006.
6. Provide protection of the trap seals for all floor drains subject to infrequent use. Reference Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson.
11/13/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/16/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/28/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
11/28/2007 CINDY AGUILAR REJECT SHELF Completed