Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM04098
Parcel: 112062350

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04098
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2007 STEVE SHIELDS ZONING REVIEW Approved
10/18/2007 PAUL MACHADO ENGINEERING REVIEW Approved
10/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/19/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/19/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water for the lavatory is limited to 110 degrees Fahrenheit.
2. Show the location of the water service shutoff valve. The valve shall be accessible at all times.
3. Show the cold water outlets on the right side of the lavatory and the mop sink.
10/19/2007 ROBERT SHERRY WATER REVIEW Denied Clarify the location of the water meter and the backflow preventer. The site plan shows the water meter approximately 40 feet from the building.
10/22/2007 DAVE MANN FIRE REVIEW Approved
10/23/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE DEIGN AND LOAD CALCULATIONS FOR CEILING
2. PROVIDE WEIGHT AND STRUCTURAL DESIGN FOR CEILING MOUNTED WATER HEATER
3. PLEASE DELETE TYPE "A" OCCUPANCY REFERENCE FOR TENANTS 2, 3 AND 4
10/26/2007 GERRY KOZIOL WWM REVIEW Approved
11/02/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review