Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04096
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/18/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 10/19/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/19/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/19/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the temperature of the hot water for the lavatory is limited to 110 degrees Fahrenheit. 2. Show the location of the water service shutoff valve. The valve shall be accessible at all times. 3. Show the cold water outlets on the right side of the lavatory and the mop sink. |
| 10/19/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | Clarify the location of the water meter and the backflow preventer. The site plan shows the water meter approximately 60 feet from the building. |
| 10/22/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/23/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE DEIGN AND LOAD CALCULATIONS FOR CEILING 2. PROVIDE WEIGHT AND STRUCTURAL DESIGN FOR CEILING MOUNTED WATER HEATER 3. PLEASE DELETE TYPE "A" OCCUPANCY REFERENCE FOR TENANTS 2, 3 AND 4 |
| 11/02/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/02/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |