Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T07CM04089
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2008 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS T07CM04089 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html GENERAL NOTES: " Show a code reference to the International Residential Code on the drawings. FOUNDATION PLANS: 1. Show a 3'x 3' foundation under the posts located at the dwelling walls, R309.3 & R401.2. 2. Provide a landing or floor surface at the slider door. A landing must be at least as wide as the door it serves and 36" in the direction of travel, R311.4.3. 3. Show compliance with termite treatment, R320 as amended. 4. Note that grade away from foundations shall fall min 6" within the first 10', R401.3. 5. Note on the drawings the allowable soil bearing pressure used in the design of the footings, or state that the assumed value of 1500 PSF is being used per Table R401.4.1 if a soils report is not provided. FLOOR PLANS: 1. Show tempered glass when located 24" of doorways, R308.4. STRUCTURAL PLANS: 1. Provide detail for bracing trusses at gable ends to prevent rotation and provide lateral stability, R802.10.3. 2. Note that scissor truss installation may require using (TC) slotted ties with appropriate uplift rating at one wall connection, R802.10.5. SECTIONS - DETAILS: 1. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d. 2. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2. 3. Specify #15 water-resistive barrier over studs of all exterior walls, R703.2. 4. Show weep screeds with a minimum clearance 4" above grade or 2" above paved areas, R703.6.2.1. 5. Calculate the attic ventilation area using 1 to 150 of attic area in compliance with R806.2. Note that upper space vents provide 50% to 80% of the required ventilating area when applying the reduced area calculation, or show a one perm rated vapor barrier installation. 6. Show a minimum 1" ventilation clearance between ceiling insulation and roof sheathing if insulation is attached to truss bottom cords and eave venting is used, R806.3. This may be accomplished w/ baffles. PLUMBING PLANS: 1. The City of Tucson has adopted the 2006 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The Plumbing Plan should reference this code. 2. Note and specify all piping materials, UPC 301.1.1. 3. Provide pressure and temperature relief valve at water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down, UPC 608.5. 4. Clarify the point of connection of the new hot and cold water lines by showing the water heater. Show the 1" service pipe from the water heater to the meter UPC 610.8, Table 6-6. 5. Provide pressure and temperature relief valve at water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down, UPC 608.5. 6. Show an upper terminal cleanout at each horizontal drainage pipe greater than 5'(all drains with a sink) UPC 707.4. 7. Show a two-way cleanout for the building at the lower end, UPC 719.0. 8. Revise the BTU demand showing the dryer load, and revise the size of the supply pipe to 1-1/4", UPC 1217.2, & Table 12-7. MECHANICAL PLANS: 1. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1. Show R-4.2 insulation when ducts are located in an unconditioned space (chase) inside the thermal envelope, IECC 503.2.7 (City of Tucson Amended). 2. Provide an equipment specification list including a cooling capacity, M1302.1. 3. Gas appliances shall comply with ARIZONA STATE PLUMBING CODE combustion air requirements or Chapter 17, 2003 IRC. Show compliance for all appliances. Confined spaces require a minimum of two 100 SQ. IN. openings, M1702.2. 4. Flues connected to more than one appliance shall be not less than the area of the largest connector plus 50% of the additional connectors. Water heater typical - 3" flue. Furnace - 4" flue. See IRC section M1805.3. ELECTRICAL PLANS: 1. Provide an electrical riser diagram showing a sub-panel from the main service, or a new service entrance, E3303. Note the grounding and bonding method, E3507. Metallic gas lines must be bonded and shall not be used as the primary grounding method, E3508. 2. Show a new sub-panel feeder conductor and conduit size, E3605. Show sub-panel feeder over-current protection (breaker size), E3605.5. 3. Show the location of the panel on the Electrical Plan, E3501.6.2 & E3605.8. 4. Bathroom receptacles shall be on a separate 20 AMP circuit with no outlets at other locations, E3603.4. 5. Provide an exterior outlet at grade level located at both the front and back of the dwelling, E3801.7. These outlets shall be GFCI protected E3802.3. 6. Note that at least one 20 AMP branch circuit shall be installed to serve the laundry room and this circuit shall have no outlets at other locations, E3603.3 and 3801.8. 7. Hallways of 10' or more in length require a receptacle, E3801.10. 8. Note that combination type arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.12. OUTDOOR LIGHTING CODE 1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. 2. Provide cut sheets for all full cut-off fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 12/26/2007 | SEPTIC APPROVAL | WWM | REVIEW | Denied | DEQ:NEED DESIGN & FEE FOR SEPTIC REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/10/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 01/10/2008 | SHANAE POWELL | REJECT SHELF | Completed |