Permit Number: T07CM04080
Parcel: 138133130

Address:
5901 S FIESTA AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM04080
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2007 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: November 14, 2007
SUBJECT: Building Plan
TO: City of Tucson Parks and Recreation - Sam Camacho
LOCATION: 5901 S Fiesta Ave, T15S, R13E, Section 12, Ward 1
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07CM04080 (First Review)


RESUBMITTAL REQUIRED: Building Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed building plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the next submittal of the Building Plans.
2. Property appears to be impacted by FEMA, special flood hazard area - Zone AE. Calculated base flood elevation is required for each individual light post and junction box. All electrical components must be elevated a minimum of one foot (1') above calculate base flood elevation. OR
3. Electrical engineer must provide certification of flood proofing for each individual light post and junction box. Certification is to ensure that all electrical components are protected to ensure safety to life and property in the event of a flood. All electrical components are to be protected against inundation of floodwaters.
4. Verification and approval from Linda Buczynski, Development Services.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
12/13/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/13/2007 SUE REEVES OUT TO CUSTOMER Completed