Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04080
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/23/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide cut sheets and structural analysis for the pole design. |
10/23/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04080 10/23/07 1. TEP available fault current for single-phase underground 200A services are 22,000 with a minimum of 45' secondary length. Such length is less than this according to scaled plans. THIS COMMENT WAS MADE ON THE FIRST REVIEW. There is still less than 45' on the TEP secondary. TEP AFC refers to the current available at the metering equipment for single phase customers. See SR-510. 2. Rating of equipment is 22K minimum according to Power Riser Diagram, but Series rated notes specifies 65K/10k. Please clarify. 3. Detail and calculations for pole and foundation shall be prepared and sealed by a Registered Structural Engineer. THIS COMMENT WAS MADE ON THE FIRST REVIEW. Plans will be approved for construction after this comment is satisfied. See Structural comments. |
11/08/2007 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review | |
11/08/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |