Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04080
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/17/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
10/17/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
10/17/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04080 10/17/07 1. TEP available fault current for single-phase underground 200A services are 22,000 with a minimum of 45' secondary length. Such length is less than this according to scaled plans. Please provide AFC, fault calculations, and fault current rating of new service pedestal. 2. Detail and calculations for pole and foundation shall be prepared and sealed by a Registered Structural Engineer. |
10/23/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
10/23/2007 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
10/23/2007 | GBONILL1 | ENGINEERING | REVIEW | Needs Review |