Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM04064
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/08/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/08/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/08/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 10/08/2008 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Provide load calcultions fpr panels A and B, inorder to verify individual circuit loads and total loads for panels. Ray T Majuta DSD City of Tucson Electrical Plan Ck 10/08/08 |
| 10/08/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | The maximum demand for a 1" water meter is limited to 25 GPM by Tucson Water. |
| 10/08/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/10/2008 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/10/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |