Permit Number: T07CM04064
Parcel: 11445262E

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM04064
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
10/08/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/08/2008 DAVE MANN FIRE REVIEW Approved
10/08/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/08/2008 JASON GREEN ENGINEERING REVIEW Approved
10/08/2008 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Denied Provide load calcultions fpr panels A and B, inorder to verify individual circuit loads and total loads for panels.

Ray T Majuta
DSD City of Tucson
Electrical Plan Ck
10/08/08
10/08/2008 ROBERT SHERRY WATER REVIEW Denied The maximum demand for a 1" water meter is limited to 25 GPM by Tucson Water.
10/08/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/10/2008 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/10/2008 DELMA ROBEY OUT TO CUSTOMER Completed