Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04063
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/16/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/16/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
10/16/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04063 10/16/07 1. Provide wire size, description, and CB for Tornados on Ckt R-25,27. 2. Provide wire size for Ckt R1-1. 3. Condensing Unit for Ice Maker is on Ckt R-17,19 on Power Floor Plan. This is a Soda Maker on the panel schedule. 4. Same as Comment #3 above Ckt R-13,15. 5. Tap to New Panel R1 is undersized. Reference NEC 240.21 (B) (1) (1) (b). 6. #8 GND in Conduit 4 is undersized. Reference NEC 250.122. |
10/16/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/16/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | . |
10/16/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/16/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
10/16/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
10/16/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
10/16/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |