Permit Number: T07CM04063
Parcel: 12906523A

Address:
3031 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04063
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2007 STEVE SHIELDS ZONING REVIEW Approved
10/16/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/16/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04063 10/16/07

1. Provide wire size, description, and CB for Tornados on Ckt R-25,27.
2. Provide wire size for Ckt R1-1.
3. Condensing Unit for Ice Maker is on Ckt R-17,19 on Power Floor Plan. This is a Soda Maker on the panel schedule.
4. Same as Comment #3 above Ckt R-13,15.
5. Tap to New Panel R1 is undersized. Reference NEC 240.21 (B) (1) (1) (b).
6. #8 GND in Conduit 4 is undersized. Reference NEC 250.122.
10/16/2007 ROBERT SHERRY WATER REVIEW Approved
10/16/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Approv-Cond .
10/16/2007 GERRY KOZIOL WWM REVIEW Approved
10/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/16/2007 PAUL MACHADO ENGINEERING REVIEW Approved
10/16/2007 DAVE MANN FIRE REVIEW Approved
10/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed