Permit Number: T07CM04047
Parcel: 10709092A

Address:
515 W KELSO ST

Review Status: Completed

Review Details: MODULAR BUILDINGS

Permit Number - T07CM04047
Review Name: MODULAR BUILDINGS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2007 LOREN MAKUS ENGINEERING REVIEW Approved
10/12/2007 MICHAEL ST. PAUL ZONING REVIEW Passed
10/16/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm04047 10/16/07

1. Provide a grounding electrode system at the service entrance.
2. Address the grounding requirements for Second Building per NEC 250.32.
3. Document disconnecting means at the modular panels. Reference NEC 225.31.
4. Define the "Specialty Systems" run to the classroom wing. Specify the termination of the conduit at both ends. If the intent is for future use, designate so on the plans, otherwise provide more information.
5. Apply for an overhead electrical service waiver.
10/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/16/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE THE SETBACS FROM THE STRUCTURE TO THE PROPERTY LINE.

2. NOTE THAT 2 EXITS ARE REQUIRED FROM THE STRUCTURE. BOTH WILL HAVE TO BE ACCESSIBLE (RAMP).
10/16/2007 RSHERRY1 WWM REVIEW Passed No connection to the public sewer
10/16/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/16/2007 ROBERT SHERRY WATER REVIEW Passed
12/17/2007 DAVE MANN FIRE REVIEW Approved
12/17/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review