Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04011
Parcel: 11712098A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04011
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2007 TERRY STEVENS ZONING REVIEW Approved
10/11/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/11/2007 DAVE MANN FIRE REVIEW Approved
10/12/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/12/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04011 10/12/07

1. Provide an electrical circuit for the new Water Heater. Reference Sheet P-2.
2. Account for the removal of the Instahot.
3. The electrical load on Ckt 7, 2880VA, would be 24A, too large for this 20A circuit. Please double check all electrical loads for accuracy.
4. Clarify voltage of Panel LPH19. Top of schedule indicates 277V, but totals are divided by 120. Also note that if it is 277 to ground, the phase-to-phase voltage would be 480V.
5. If Panel LPH19 is 120V to ground, then it may be overloaded, especially adding 25% for continuous load and largest motor.
10/12/2007 ROBERT SHERRY WATER REVIEW Approved
10/12/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/12/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the water heater is attached to the building structure.
2. An indirect waste receptor shall not be installed inside of a cabinet.
3. The termination of a T&P relief requires an air gap, not an air break. Reference Section 804.1, UPC 2006, as amended by the City of Tucson.
4. Lavatory faucets shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water or shall be designed to deliver no more than an average of one-half gallon of water per minute at a pressure of eighty PSI. Reference ARS 45-313.
10/26/2007 DROBEY1 WWM REVIEW Needs Review
10/26/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2007 DELMA ROBEY APPROVAL SHELF Completed
10/26/2007 DELMA ROBEY OUT TO CUSTOMER Completed
10/26/2007 DELMA ROBEY REJECT SHELF Completed