Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04011
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/11/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
10/11/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
10/11/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
10/12/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
10/12/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04011 10/12/07 1. Provide an electrical circuit for the new Water Heater. Reference Sheet P-2. 2. Account for the removal of the Instahot. 3. The electrical load on Ckt 7, 2880VA, would be 24A, too large for this 20A circuit. Please double check all electrical loads for accuracy. 4. Clarify voltage of Panel LPH19. Top of schedule indicates 277V, but totals are divided by 120. Also note that if it is 277 to ground, the phase-to-phase voltage would be 480V. 5. If Panel LPH19 is 120V to ground, then it may be overloaded, especially adding 25% for continuous load and largest motor. |
10/12/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/12/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/12/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the water heater is attached to the building structure. 2. An indirect waste receptor shall not be installed inside of a cabinet. 3. The termination of a T&P relief requires an air gap, not an air break. Reference Section 804.1, UPC 2006, as amended by the City of Tucson. 4. Lavatory faucets shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water or shall be designed to deliver no more than an average of one-half gallon of water per minute at a pressure of eighty PSI. Reference ARS 45-313. |
10/26/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
10/26/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/26/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
10/26/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
10/26/2007 | DELMA ROBEY | REJECT SHELF | Completed |