Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM04010
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/11/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/11/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04010 10/11/07 1. Provide an electrical circuit for the fixtures to the left (east, west?) of the abandoned conduit, Ckt 41. Otherwise 22 amps overloads the 20A circuit (without break in conduit). 2. Note that there are 43,560SF/acre. Thus, the Outdoor Lighting Code Compliance calculations are too conservative. A correction would give the Owner a better sense of spare allowable lumens there are on this site. 3. Note that Option 2 allows 300,000 FCO lumens 4. Put the following note on the plans: "Special inspection required per Tucson Lighting Code Section 16." |
| 10/11/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 11/13/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/13/2007 | CAGUILA1 | FIRE | REVIEW | Needs Review | |
| 11/13/2007 | CAGUILA1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/13/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |