Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM04009
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/11/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/11/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 07CM04007 10/11/07 1. Ckt 41 is overloaded at 2687VA, or 22 amps. Overloads the 20A circuit (without break in conduit). 2. Lumens for Fixture D appear to be too high for this 175W fixture. 3. Fixture D on pole, not under canopy. See Note 1. 4. There are 43,560SF/acre. Calculations for allowable lumens too conservative to give Owner a true picture of allowable spare. 5. Account for Fixture C. 6. Put the following note on the plans: "Special inspection required per Tucson Lighting Code Section 16." 7. Option 2 allows 300,000 FCO luments per acre. |
| 10/11/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 11/13/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/13/2007 | CAGUILA1 | FIRE | REVIEW | Needs Review | |
| 11/13/2007 | CAGUILA1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/13/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |