Permit Number: T07CM04008
Parcel: Unknown

Address:
3797 S KOLB RD

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM04008
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/11/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04005 10/11/07

1. Fixture D, pole mounted, would not be under a canopy. Reference Outdoor Lighting Code Compliance Note 5.
2. It does not appear that Fixture A is under a canopy. Reference Outdoor Lighting Code Compliance Note 5.
3. It appears that the total should read "144,000", not 1,440,000.
4. Put the following note on the plans: "Special inspection required per Tucson Lighting Code Section 16."
10/11/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/13/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/13/2007 CAGUILA1 FIRE REVIEW Needs Review
11/13/2007 CAGUILA1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/13/2007 CINDY AGUILAR OUT TO CUSTOMER Completed