Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/11/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 07CM04007 10/11/07

1. Ckt 41 is overloaded at 2687VA, or 22 amps. Overloads the 20A circuit (without break in conduit).
2. It appears that the site lumen total should read "144,000", not 1,440,000.
3. Fixture D on pole, not under canopy. See Note 5.
4. Canopy for Fixture A not seen from plans.
5. Account for Fixture B.
6. Put the following note on the plans: "Special inspection required per Tucson Lighting Code Section 16."
11/13/2007 CAGUILA1 ENGINEERING REVIEW Needs Review
11/13/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/13/2007 CAGUILA1 FIRE REVIEW Denied
11/13/2007 CAGUILA1 ZONING REVIEW Needs Review