Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM04007
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/11/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/11/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 07CM04007 10/11/07 1. Ckt 41 is overloaded at 2687VA, or 22 amps. Overloads the 20A circuit (without break in conduit). 2. It appears that the site lumen total should read "144,000", not 1,440,000. 3. Fixture D on pole, not under canopy. See Note 5. 4. Canopy for Fixture A not seen from plans. 5. Account for Fixture B. 6. Put the following note on the plans: "Special inspection required per Tucson Lighting Code Section 16." |
| 11/13/2007 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review | |
| 11/13/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/13/2007 | CAGUILA1 | FIRE | REVIEW | Denied | |
| 11/13/2007 | CAGUILA1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/13/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |