Permit Number: T07CM03974
Parcel: 13601008J

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM03974
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review Impact Fee's Do Apply; East District; 15,000 Square Feet of Storage/Warehouse; $15,342.50 ***Please be aware Impact fees will increase to $30,635.00 if permit not pulled by January 15, 2008***
01/11/2008 DAVE MANN FIRE REVIEW Denied Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards, and the propose type and height of storage.
4. The density required of the water supply.
01/14/2008 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Relocate the backflow preventer or provide a letter from Tucson Water that allows the backflow preventer to be located in the location shown on the drawings. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
01/15/2008 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2008 DELMA ROBEY APPROVAL SHELF Completed
01/15/2008 DELMA ROBEY OUT TO CUSTOMER Completed
01/15/2008 DELMA ROBEY REJECT SHELF Completed