| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | Impact Fee's Do Apply; East District; 15,000 Square Feet of Storage/Warehouse; $15,342.50 ***Please be aware Impact fees will increase to $30,635.00 if permit not pulled by January 15, 2008*** |
| 01/11/2008 | DAVE MANN | FIRE | REVIEW | Denied | Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards, and the propose type and height of storage. 4. The density required of the water supply. |
| 01/14/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Relocate the backflow preventer or provide a letter from Tucson Water that allows the backflow preventer to be located in the location shown on the drawings. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
| 01/15/2008 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/15/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 01/15/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 01/15/2008 | DELMA ROBEY | REJECT SHELF | Completed |