12/04/2007 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity: T07CM03970 2nd Review
Date: 12/05/07

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

I. GENERAL REQUIREMENTS:
" Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

II. STRUCTURAL PLANS:
" Specify manufacturer and series for glue-lams and "I" joists, R802.1.
" Specify the size and spacing of the rafters over the causeway.

III. SECTIONS - DETAILS:
" Provide cross-references for all details to the floor plan and framing plans.

IV. PLUMBING PLAN:
" As of June 13, 2007 the City of Tucson has adopted the 2006 UPC with amendments. The plans should reference this codes, or appeal to the Building Official for 1994 UPC-design approval.
" Provide vent piping through the roof so that the aggregate cross-sectional area shall not be less than that of the largest required building sewer, UPC 904.1.

V. ELECTRICAL PLAN:
" Provide an electrical riser diagram that accurately depicts the installation with feeder conductor sizes and conduit sizes, E3303, E3507. (Will the new sub-panel receive power from the existing panel on the house, and will the feeders supplying power to the existing panel be underground?)

If you have any questions please contact:
Clayton Trevillyan
(520) 837-4913
City of Tucson Residential Plan Review