Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03953
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/13/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
11/15/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/21/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/21/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that the mop sink, service sink faucet, and the pre-rinse faucet have 3rd party listings and comply with all of the applicable standards referenced in the 2006 UPC. Reference Section 301.1.1, UPC 2006. 2. Revise the support detail for the water heater to show how the plywood platform is braced along the high wall and front edge of the platform. 3. The dump sink, P-6, shall not be indirectly wasted. Reference Sections 304.0 and 801.2, UPC 2006. |
11/23/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/26/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide listing information for the proposed backdraft damper on the exhaust fan discharge that shows it is suitable for the intended use. Reference Section 506.5, IMC 2006. |
11/26/2007 | HEATHER THRALL | ZONING | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/30/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
11/30/2007 | CINDY AGUILAR | REJECT SHELF | Completed |