Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM03953
Parcel: 12404102B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03953
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/15/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/21/2007 ROBERT SHERRY WATER REVIEW Approved
11/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that the mop sink, service sink faucet, and the pre-rinse faucet have 3rd party listings and comply with all of the applicable standards referenced in the 2006 UPC. Reference Section 301.1.1, UPC 2006.
2. Revise the support detail for the water heater to show how the plywood platform is braced along the high wall and front edge of the platform.
3. The dump sink, P-6, shall not be indirectly wasted. Reference Sections 304.0 and 801.2, UPC 2006.
11/23/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/26/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide listing information for the proposed backdraft damper on the exhaust fan discharge that shows it is suitable for the intended use. Reference Section 506.5, IMC 2006.
11/26/2007 HEATHER THRALL ZONING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/30/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
11/30/2007 CINDY AGUILAR REJECT SHELF Completed