Permit Number: T07CM03953
Parcel: 12404102B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03953
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2007 MARTIN BROWN FIRE REVIEW Approved
10/04/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/22/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The use of the IPC for the plumbing design will require an appeal to the building official.
2. Provide material standards for all plumbing fixtures (e.g. sinks) being provided by others. Reference Section 402, IPC 2006.
3. Coordinate the design of the support shown in the water heater schematic (detail 1/P2) with detail L/A1 along with the size of the water heater relative to the size of the support shelf. Reference Section 106.3.1, IPC 2006.
4. Coordinate the waste and vent diagram with the plumbing floor plan. Reference Section 106.3.1, IPC 2006.
5. Complete the DCW and DHW isometric to include the rest of the installation. Reference Section 106.3.1, IPC 2006.
6. The water pressure calculations show an 11-PSI drop across the 2" meter. If the total demand that this meter is supplying exceeds the maximum demand of 80 GPM allowed by Tucson Water for a 2" meter, provide a larger meter for the building or a separate meter for this suite.
7. Specify the double check valve backflow preventer to be used for the directly connected appliances (i.e. which ASSE standard is it to meet?). Reference Section 106.3.1, IPC 2006.
8. Provide information to show that the existing grease interceptor complies with the requirements of Section 1003.3.4, IPC 2006 and that the addition of the proposed fixture will not exceed the rated flow for the interceptor.
9. Show that the influent to the grease interceptor complies with Section 1003.3.1, IPC 2006.
10. Provide information to show why the floor sink located under the rotisserie, the pre-rinse sink, and any other fixtures or equipment that might allow grease to be introduced into the building drain is not connected to a grease interceptor. Reference Section 1003.3.1, IPC 2006.
10/23/2007 ROBERT SHERRY WATER REVIEW Denied Show that the total demand served by the existing 2" reduced pressure backflow preventer is in compliance with the manufacturer's listing information.
10/23/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2006.
2. ASHRAE 62N is no longer in force; use ASHRAE 62-1-2004 ventilation calculations if the 2006 IMC ventilation calculations are not being used. If the default occupant densities and combined outdoor air rates of ASHRAE 62-1-2004 are not being used, provide justification for the ventilation of the space. Reference Section 403.2, IMC 2006, as amended by the City of Tucson.
3. Justify the use of a zone air distribution effectiveness (Ez) value of 1 instead of 0.8. Reference Table 6-2 ASHRAE 62-1-2004.
4. Show that the specified exhaust fans EF-1 and EF-2 (and the approved equivalents) comply with the requirements of Section 506.5, IMC 2006 or UL-762.
5. Show how the proposed installation of exhaust fans EF-1 and EF-2 will not result in the discharge of grease from the grease reservoir during rain events occurring when the fans are not operating. Reference Section 506.5.2, IMC 2006.
6. Show that the clearances for the Type I hoods comply with Section 507.9, IMC 2006. (See architectural note on A1 floor plan.)
7. Provide structural calculations and details to show that the Type I and Type II hood s are supported from the building structure in accordance with Section 507.6, IMC 2006.
10/25/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. DETAIL "C/A-1" NEEDS VERTICAL BAR AS PER ANNSI 604.5.1
2. TOILET ROOMS NEEDS 4' HIGH WASHABLE WALL WAINSCOATING AS PER SECTION 1210.2
3. PROVIDE ROOM FINISH AND DOOR SCHEDULES
10/29/2007 GERRY KOZIOL WWM REVIEW Approved
10/30/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Provide disconnecting means for Equipment E10, or justify otherwise.
2. Provide service load calculations for all occupancies permitted as of this time.