Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM03928
Parcel: 133231340

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03928
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2007 MARTIN BROWN FIRE REVIEW Approved
10/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03928 10/02/07

1. Provide electrical requirements for water heater. Demonstrated that this unit is cord-connected.
10/02/2007 ROBERT SHERRY WATER REVIEW Approved
10/02/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE BREAKDOWN OF HOW 20% COST OF CONSTRUCTION IS BEING APPLIED FOR ACCESSIBILITY PER SECTION 3409 OF THE IBC.

2) PROVIDE SECTION DETAILS FOR ACCESSIBLE FACILITIES SUCH AS THE BREAKROOM SINK.

3) THIS AREA APPEARS TO BE INCREASING THE OCCUPANT LOAD (CHANGE FROM S TO B) THEREFORE PLEASE PROVIDE OCCUPANCY CALCULATIONS FOR ENTIRE AREA THAT SHARES RESTROOMS SHOWING COMPLIANCE WITH CHAPTER 29 OF THE IBC.
10/02/2007 RSHERRY1 WWM REVIEW Passed
10/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/03/2007 CAGUILA1 ENGINEERING REVIEW Needs Review
10/03/2007 CAGUILA1 ZONING REVIEW Needs Review
10/03/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review