Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM03912
Parcel: 141153540

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03912
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2007 TERRY STEVENS ZONING REVIEW Approved
10/01/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/01/2007 MARTIN BROWN FIRE REVIEW Approved
10/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Complete recirculation of ventilation air from toilet rooms is prohibited. Reference Section 403.2.1 (3), IMC 2006.
10/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/02/2007 ROBERT SHERRY WATER REVIEW Approved
10/02/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) INCLUDE GAUGE OF STEEL IN DETAIL FOR HARD LID CEILING.

2) PROVIDE SUPPORT DETAILS FOR WATER HEATER OVER WOMENS RESTROOM. INCLUDE NECESSARY LIVE LOAD INFORMATION THAT MAY BE REQUIRED FOR SERVICE OF EQUIPMENT.

3) PLEASE ADD WHEEL CHAIR DUDE TO DETAIL A5/A6.1 IN THE FUTURE (KEEPS CONTRATORS FROM ARGUING WITH INSPECTORS).
10/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/04/2007 VFLORES1 WWM REVIEW Needs Review
10/04/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review