Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03912
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/01/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 10/01/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 10/02/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Complete recirculation of ventilation air from toilet rooms is prohibited. Reference Section 403.2.1 (3), IMC 2006. |
| 10/02/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/02/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/02/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) INCLUDE GAUGE OF STEEL IN DETAIL FOR HARD LID CEILING. 2) PROVIDE SUPPORT DETAILS FOR WATER HEATER OVER WOMENS RESTROOM. INCLUDE NECESSARY LIVE LOAD INFORMATION THAT MAY BE REQUIRED FOR SERVICE OF EQUIPMENT. 3) PLEASE ADD WHEEL CHAIR DUDE TO DETAIL A5/A6.1 IN THE FUTURE (KEEPS CONTRATORS FROM ARGUING WITH INSPECTORS). |
| 10/02/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/04/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 10/04/2007 | VFLORES1 | WWM | REVIEW | Needs Review |