Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM03900
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03900
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2007 STEVE SHIELDS ZONING REVIEW Approved
09/28/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide an auxiliary drain or secondary drain for the fan coil unit.
2. Show how the fan coil is attached to the structure.
3. Where is the condensate terminating?
09/28/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03900 9/28/07

1. Clarify voltage of Panel A. Panel schedule and calcs indicate 208V. Line diagram calls for 240V.
09/28/2007 ROBERT SHERRY WATER REVIEW Approved
09/28/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Approved
09/28/2007 RSHERRY1 WWM REVIEW Passed
09/28/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/28/2007 JASON GREEN ENGINEERING REVIEW Approved
10/09/2007 CAGUILA1 FIRE REVIEW Needs Review
10/09/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review