Permit Number: T07CM03898
Parcel: 13317062A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03898
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2007 STEVE SHIELDS ZONING REVIEW Approved
09/28/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/28/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03898 9/28/07

1. Provide TEP available fault current, fault calculations, and fault current rating of new panel.
2. Indicate location of service on scaled drawing (either by dimension or per scale).
09/28/2007 ROBERT SHERRY WATER REVIEW Approved
09/28/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Approved
09/28/2007 JASON GREEN ENGINEERING REVIEW Approved Area determined to be outside of the COT FH area per a manning section.
09/28/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/28/2007 DAVE MANN FIRE REVIEW Approved
10/03/2007 GERRY KOZIOL WWM REVIEW Approved
10/03/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review