Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03877
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/27/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
09/27/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. See detail 1/M1. |
09/27/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
09/27/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/27/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/27/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
09/27/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/28/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/01/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/01/2007 | MARTIN BROWN | FIRE | REVIEW | Approved |