Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM03877
Parcel: 12404100A

Address:
845 N PARK AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03877
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2007 TERRY STEVENS ZONING REVIEW Approved
09/27/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. See detail 1/M1.
09/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
09/27/2007 ROBERT SHERRY WATER REVIEW Approved
09/27/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Approved
09/27/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/27/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/28/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/01/2007 GERRY KOZIOL WWM REVIEW Approved
10/01/2007 MARTIN BROWN FIRE REVIEW Approved