Permit Number: T07CM03875
Parcel: 123061380

Address:
2424 E ADAMS ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03875
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2008 GERRY KOZIOL WWM REVIEW Denied NEEDS DEQ REVIEW OF GRAYWATER SYSTEM
02/08/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity: T07CM03875 2nd review
Date: 2/08/08

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

I. GENERAL REQUIREMENTS:
" Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

II. FLOOR PLANS:
" Clarify intended use of existing window over kitchen sink. Will it remain unchanged?

III. FOUNDATION PLANS:
" Specify elevation changes in finished floor heights as well as height of steps.
" Provide venting for under-floor areas, 408.1.
" Specify size of access to under-floor area, 408.4.
" Provide cross-section detail for under-floor access design.

IV. STRUCTURAL PLANS:
" Provide roof framing information (i.e. Rafter size and spacing) for existing roof over the proposed garage enclosure. Existing conditions may not be acceptable for the change of use. Structural elements must meet current code requirements.

V. PLUMBING PLAN:
" Polybutylene is not an approved water piping material, UPC 301.1.1.
" Fixture unit schedule is based on International fixture units. Clarify which code (IRC or UPC) this project is designed under.
" Provide a water meter and service line designed to accommodate the proposed demand, UPC Table 6-6.
" If new gas lines will not be installed on this project, provide the electrical information for the tankless water heater.

VI. MECHANICAL PLAN:
" Specify the intended service area to meet the working space requirements of M1305.1 for appliances located in the mechanical closet. Verify the available area for both the heat pump and the water heater.
" Provide an equipment specification list with the make and model of all mechanical equipment, M1302.1. Specify the make and model of the tankless water heater.

VII. ELECTRICAL PLAN:
" Show receptacle outlets at wall spaces 2' or more so that no point along the wall (excluding door openings) is more than 6' from a receptacle outlet, E3801.2. A garage has different wiring requirements compared to living space. To convert the garage to a bedroom, additional receptacles will be required.

If you have any questions please contact:
Clayton Trevillyan
(520) 837-4913
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2008 CPIERCE1 OUT TO CUSTOMER Completed