Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03868
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/26/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2006. |
| 09/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03638 9/26/07 1. VA per phase at 125% demand for 40 FLA AC WOULD BE 6000, not 4371. 2. Please reconsider only 180VA per outlet, or 720 per quad for electrical loading on quad receptacles. |
| 09/26/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/26/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/26/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the temperature of the hot water supply to the public lavatory is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. Provide the minimum plumbing fixtures (e.g. a drinking fountain) per Chapte 29, IBC 2006. |
| 09/28/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 09/28/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Approved | 1. PROVIDE LETTER OF APPEAL TO THE BUILDING OFFICIAL FOR THE USE OF BOTTLED WATER V. REQUIRED DRINKING FOUNTAIN. |
| 09/28/2007 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
| 09/28/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/28/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 09/28/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 09/28/2007 | DELMA ROBEY | REJECT SHELF | Completed |