Permit Number: T07CM03858
Parcel: 11203347E

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM03858
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Passed
09/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03858 9/26/07

1. Complete the electrical design. See comments below.
2. Indicate whether branch circuits on sub-panel are existing, or new with this construction. If new, provide Electrical Plan for the building.
3. Provide conduit and conductor size and type.
4. Provide Electrical Line Diagram.
5. Provide utility available fault current, fault calculations, and fault current rating of all equipment.
6. Provide location of all equipment on Electrical Site Plan.
7. Provide for equipment grounding per NEC 250 Part VI.
8. Specify the grounding electrode system.
9. Address the requirements of NEC 250.32, as necessary.
10. See the attached "Electrical Permitting Requirements."