Permit Number: T07CM03821
Parcel: 12701002C

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM03821
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2007 ROBERT SHERRY WATER REVIEW Denied The water demand (288 fixture units, 107 GPM) for this building exceeds the allowed flow for a 2" meter. Provide a letter from Tucson Water allowing the use of this size meter or revise the design.
10/26/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2007 DELMA ROBEY APPROVAL SHELF Completed
10/26/2007 DELMA ROBEY OUT TO CUSTOMER Completed
10/26/2007 DELMA ROBEY REJECT SHELF Completed