Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T07CM03794
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/11/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/18/2007 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T07CM03794 10/24/07 963 N. CORINTH AVE. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FLOOR PLANS: 1. THE WALL ADJACENT THE "STACKED W/D" IS INDICATED AS BEING PER DETAIL 3 ON PAGE 7. WHAT DOES THE HEADER IN THE DETAIL SPAN? 2. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER WITH CERAMIC TILE, OR A LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R307.2 SECTIONS - DETAILS - MISC. NOTES: 1. 1 / 7 ; PLEASE SPECIFY THE CONNECTION OF THE SINGLE TOP PLATE AT THE JOINTS. SEE R602.3.2 . 2. 1 / 7 ; PROVIDE THE DIAMETER OF THE PINS @ THE BOTTOM PLATE. 3. 2 / 7 ; PLEASE CHANGE THE DOUBLE HANGER ON THE SINGLE RAFTER TAILS TO A SINGLE HANGER. PLUMBING PLANS: 1. NOTE AND SPECIFY ALL PIPING MATERIALS. 2. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND, MAXIMUM DEVELOPED LENGTH, AND DISTRIBUTION DRAWING.. 3. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWERHEADS 3 GALLONS PER MINUTE. 4. SHOW THE ROUTE OF THE TEMPERATURE AND PRESSURE RELIEF LINE FROM THE WATER HEATER. 5. GAS PLAN AND ISOMETRIC / 7 ; THE ¾" AND 1" SUPPLYING THE FURNACE APPEARS TO BE INADEQUATE. SEE '06 UPC TABLE 12-8. MECHANICAL PLANS: 1. PLEASE ADD A NOTE RE: THE INSULATION ON THE DUCTS IN UNCONDITIONED SPACE IS REQUIRED TO BE R-8. SEE '06 IECC SECTION 503.2.7 AS AMENDED. 2. PLEASE SIZE THE DUCT FOR THE RETURN AIR SYSTEM. ELECTRICAL PLANS: 1. PROVIDE A CIRCUIT NUMBER BESIDE EACH ELECTRICAL DEVICE AND NUMBER THE CIRCUITS IN THE PANEL SCHEDULE. 2. PROVIDE ELECTRICAL LOAD CALCULATIONS. 3. PROVIDE THE TEMPERATURE RATING OF THE CONDUCTORS LISTED IN THE WIRE SIZE TABLE. 4. PROVIDE THE CONDUCTOR SIZE FOR THE EACH BREAKER USED. 5. PLEASE ADD A RECEPTACLE TO THE RIGHT OF THE REFRIGERATOR. SEE E3801.4 6. PROVIDE POWER FOR THE FURNACE AND THE WATER HEATER. 7. A RECEPTACLE IS REQUIRED WITHIN 6 FEET OF THE SOUTH WEST BEDROOM CLOSET DOOR. PLEASE CHECK THE LOCATION OF ALL RECEPTACLES TO CONFIRM LOCATION PER E3861.2.1 8. WILL A DOOR BE USED ON THE FURNACE / WATER HEATER ROOM? CONFIRM THE SUB-PANEL WILL HAVE WORKING SPACE AND CLEARANCE IN ACCORDANCE WITH E3801.2.1 AND E3801.2.2 . IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 837-4910 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/25/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 10/25/2007 | DELMA ROBEY | REJECT SHELF | Completed |