Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03784
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/19/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
09/19/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
09/20/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
09/20/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t07cm03784 9/20/07 1. When Phase A is added on Panel B (159), the total comes to 208A for this 200A panel. This was computed by taking the continuous loads at 125%, and by adding 47A to Phase A for Panel C (159). Please re-adjust. 2. Minimum font size 1/8". |
09/20/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/20/2007 | HEATHER THRALL | ZONING | REVIEW | Needs Review | |
09/20/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
09/20/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
09/21/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
09/21/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/21/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |