Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2007 DAVE MANN FIRE REVIEW Approved
09/19/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Needs Review
09/20/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
09/20/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm03784 9/20/07

1. When Phase A is added on Panel B (159), the total comes to 208A for this 200A panel. This was computed by taking the continuous loads at 125%, and by adding 47A to Phase A for Panel C (159). Please re-adjust.
2. Minimum font size 1/8".
09/20/2007 ROBERT SHERRY WATER REVIEW Approved
09/20/2007 HEATHER THRALL ZONING REVIEW Needs Review
09/20/2007 PAUL MACHADO ENGINEERING REVIEW Approved
09/20/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
09/21/2007 GERRY KOZIOL WWM REVIEW Approved
09/21/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review