Permit Number: T07CM03773
Parcel: 13315062A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03773
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) THE LAVATORY ENCROACHES ON CLEAR FLOOR SPACE AROUND WATER CLOSET. REFERENCE 2003 ANSI 117.1 SECTION 604.3.2

2) APPROVED APPEAL TO BUILDING OFFICIAL IS REQUIRED TO SUBSTITUTE BOTTLED WATER FOR DRINKING FOUNTAIN.

3) PLEASE INDICATE CORRECT UNISEX ACCESSIBLE SIGNAGE FOR RESTROOM. DETAIL A4/A6.1.
09/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/18/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03773 9/18/07

1. Water Heater is 120V per Sheet P1.1, but electrical provides 208. Coordinate with Plumbing and clarify.
09/18/2007 ROBERT SHERRY WATER REVIEW Approved
09/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a water riser diagram.
2. Show how the temperature of the hot water supply to the public lavatory is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
3. Provide listing information to show that the 2-way cleanout shown in Detail C2/P1.1 is not in violation of Section 707.6, UPC 2006.
09/19/2007 JASON GREEN ENGINEERING REVIEW Approved
09/19/2007 HEATHER THRALL ZONING REVIEW Approved
09/19/2007 DAVE MANN FIRE REVIEW Approved
09/28/2007 DROBEY1 WWM REVIEW Needs Review
09/28/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2007 DELMA ROBEY APPROVAL SHELF Completed
09/28/2007 DELMA ROBEY OUT TO CUSTOMER Completed
09/28/2007 DELMA ROBEY REJECT SHELF Completed