Permit Number: T07CM03763
Parcel: 107144360

Address:
2581 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03763
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2007 DAVE MANN FIRE REVIEW Approved
09/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide design drawings sealed by an Arizona Registrant.
2. Revise the ventilation calculations per Sections 403.3 and 403.3.2, IMC 2006. Note that the storage room and the break room are not supplied with supply air from AC-1 and should not be included in the AC-1 calculations.
09/18/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03763 9/18/07

1. Provide electrical power for HP-1.
2. Water Heater, at 29A, would be 3480VA at 120V, not 1500.
3. Water Heater, at 29A, could not operate on a 20A circuit.
4. Provide a disconnecting means for both water heaters, and/or demonstrate that they are cord-connected.
5. For Phase A, 16050VA at 120V would be 134A, not 67. Phase appears overloaded. Concept applies to Phase C as well.
6. Count 25% of largest motor on panel schedule.
7. Add new heat pump to Service calculation.
8. Add water heaters to Service Load Calculations.
9. Add 7.5 KW for the Fan Coil Unit to Service Load Calculations.
10. Provide electrical line diagram including all panels on electrical service, and add them to Service Load Calculations.
09/18/2007 ROBERT SHERRY WATER REVIEW Approved
09/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1.Provide both water and waste & vent risre diagrams.
2. Show how the maximum hot water temperature for the lavatory is to be limited to 110 degrees Fahrenheit. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006
3. Provide the minimum plumbing fixtures required by Table 2902.1, IBC 2006 for business occupancy.
09/18/2007 PAUL MACHADO ENGINEERING REVIEW Approved
09/19/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
09/20/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Denied UPDATE CODE INFORMATION TO INCLUDE 2006 IBC

IN THE RESTROOM, THE EAST AND SOUTH WALL WILL BE REQUIRD TO AHVE TILE , FRP OR OTHER SUITABLE FINISH. PAIN WILL NTO QUALIFY.

UPDATE ANSI TO INCLUDE THE 2003 ANSI A117.1

REVISE DETAIL AT THE WATERCLOSET TO CORESPOND TO THE NOTES, 7"-9"
10/12/2007 VFLORES1 WWM REVIEW Needs Review
10/12/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review