Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03763
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/18/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide design drawings sealed by an Arizona Registrant. 2. Revise the ventilation calculations per Sections 403.3 and 403.3.2, IMC 2006. Note that the storage room and the break room are not supplied with supply air from AC-1 and should not be included in the AC-1 calculations. |
| 09/18/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03763 9/18/07 1. Provide electrical power for HP-1. 2. Water Heater, at 29A, would be 3480VA at 120V, not 1500. 3. Water Heater, at 29A, could not operate on a 20A circuit. 4. Provide a disconnecting means for both water heaters, and/or demonstrate that they are cord-connected. 5. For Phase A, 16050VA at 120V would be 134A, not 67. Phase appears overloaded. Concept applies to Phase C as well. 6. Count 25% of largest motor on panel schedule. 7. Add new heat pump to Service calculation. 8. Add water heaters to Service Load Calculations. 9. Add 7.5 KW for the Fan Coil Unit to Service Load Calculations. 10. Provide electrical line diagram including all panels on electrical service, and add them to Service Load Calculations. |
| 09/18/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/18/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1.Provide both water and waste & vent risre diagrams. 2. Show how the maximum hot water temperature for the lavatory is to be limited to 110 degrees Fahrenheit. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006 3. Provide the minimum plumbing fixtures required by Table 2902.1, IBC 2006 for business occupancy. |
| 09/18/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 09/19/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/20/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Denied | UPDATE CODE INFORMATION TO INCLUDE 2006 IBC IN THE RESTROOM, THE EAST AND SOUTH WALL WILL BE REQUIRD TO AHVE TILE , FRP OR OTHER SUITABLE FINISH. PAIN WILL NTO QUALIFY. UPDATE ANSI TO INCLUDE THE 2003 ANSI A117.1 REVISE DETAIL AT THE WATERCLOSET TO CORESPOND TO THE NOTES, 7"-9" |
| 10/12/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 10/12/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |