Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/26/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the new roof top unit. Reference Section 302.1, IMC 2003.
2. Neither P1 nor P2 indicate any change in the operation of the soft-serve machine. Revise the drawings to confirm that an air-cooled machine is now being installed instead of a water-cooled, soft-serve machine. Reference Section 1201.3, IMC 2006 as amended by the City of Tucson.
11/27/2007 ROBERT SHERRY WATER REVIEW Denied 1. Reduced pressure backflow prevention assemblies shall be installed directly after the water meter for buildings that have food service facilities. Show the location, model, and size of the assembly serving this tenant space. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf (Note that this refers to the backflow preventer protecting the municipal water supply from activities in the building, not a subsequent-backflow preventer as shown in detail 2/P2.)
2. Show the location and size of the water meter serving this tenant space. Reference Section 103.2.3, UPC 2006. (Note that this refers to the municipal water supply meter, not a sub-meter-as shown in detail 2/P2.)
11/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The use of a floor drain as an indirect waste receptor cannot be approved unless the proposed floor drain is designed to prevent splashing or flooding (e.g. equipped with a funnel top). Reference section 804.1, UPC 2006.
2. Provide an upper terminal cleanout for the mop sink (#51). Reference Section 707.4, UPC 2006.
3. A backflow preventer installed at a height greater than five feet above the finished floor (detail 2/P2) requires the installation of a maintenance platform. Reference Section 603.3.4, UPC 2006.
11/27/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. THIS COMMENT WAS MADE ON THE REVIEW OF 10/01/07. MUCH OF THE FONT SIZE, SUCH AS THE PANEL SCHEDULE, IS 1/16".
2. If there are other disconnecting means to the service, please provide full one-line diagram and service load calculations. THIS COMMENT WAS MADE ON THE REVIEW OF 10/01/07. Since the occcupancy is located within a larger building, with the disconnecting for both panels located in the landlord's electrical room, it would follow that this is not the only service disconnecting means to this building. It is necessary to clarify this. Please give the reviewer a call to discuss.
12/10/2007 GERRY KOZIOL WWM REVIEW Denied needs 8th floor credit evaluation