Permit Number: T07CM03750
Parcel: 11201085L

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM03750
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2008 GERRY KOZIOL WWM REVIEW Approved
02/25/2008 DAVE MANN FIRE REVIEW Approved
02/28/2008 ROBERT SHERRY WATER REVIEW Denied 1. Provide the size of the existing water meter. The calculated water demand for the proposed dwelling is 18 GPM per Appendix L, UPC 2006. The water meter shall be sized to accommodate this flow or the fire sprinkler flow, whichever is greater. A demand flow of 18 GPM through a 5/8" water meter results in an excessive pressure drop and a velocity greater than the maximum 8 FPS allowed for either plastic or copper piping. In addition, Tucson Water limits a 5/8" meter to a maximum demand of 10 GPM. Reference Sections 610.2 and 610.12, UPC 2006.