Permit Number: T07CM03740
Parcel: 10605005E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03740
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2007 DAVE MANN FIRE REVIEW Approved
09/14/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/14/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved PROVIDE DETAILS FOR FRAMING ABOVE CIELING. CLARIFY "EITHER SIDE" NOTE FOR ROCK, DO YOU MEAN BOTH SIDES?

JUSTIFY USE OF 1 HOUR FIRE SEPERATION (CODE ANALYSIS FOR OCC. SEPARATION)

PLANS NOTE THAT EXISTING CONDITION IS 1/4" GYPBOARD THAT IS NOT THE CASE.
09/24/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/24/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy (i.e. drinking fountain).
09/24/2007 ROBERT SHERRY WATER REVIEW Approved
09/24/2007 STEVE SHIELDS ZONING REVIEW Approved
09/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM03740 9/24/07

1. Show location of electrical panels for both suites. Reference NEC 240.24 (B).
11/02/2007 CAGUILA1 WWM REVIEW Needs Review
11/02/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review