Permit Number: T07CM03737
Parcel: 12613018A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03737
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2007 STEVE SHIELDS ZONING REVIEW Approved
09/14/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03737 9/14/07

1. Provide circuit for receptacles on west wall of east section.
2. Provide feeder sizes for HP units.
3. Add 25% for largest motor load on panel and service calculations. Panel A Phase A could be overloaded. Service Entrance Section #1 could be overloaded.
4. Service #2 please account for both AC's in service load calculations.
5. Provide available fault current at new Panel C.
09/14/2007 ROBERT SHERRY WATER REVIEW Approved
09/14/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/14/2007 PAUL MACHADO ENGINEERING REVIEW Approved
09/14/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plmbing fixtures required by Chapter 29, IBC 2006.
2. Specify the water heaters to be used for the lavatories.
09/14/2007 DAVE MANN FIRE REVIEW Approved
09/14/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/18/2007 CAGUILA1 WWM REVIEW Needs Review