Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03737
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/14/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
09/14/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/14/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03737 9/14/07 1. Provide circuit for receptacles on west wall of east section. 2. Provide feeder sizes for HP units. 3. Add 25% for largest motor load on panel and service calculations. Panel A Phase A could be overloaded. Service Entrance Section #1 could be overloaded. 4. Service #2 please account for both AC's in service load calculations. 5. Provide available fault current at new Panel C. |
09/14/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/14/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/14/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
09/14/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plmbing fixtures required by Chapter 29, IBC 2006. 2. Specify the water heaters to be used for the lavatories. |
09/14/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
09/14/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/18/2007 | CAGUILA1 | WWM | REVIEW | Needs Review |